8. Seismic Loads:
Seismic load shall be determined based upon a response acceleration factors S
s
=0.164,
S
1
= 0.052
Seismic Design Category “C”
Seismic Site Class “D”
9. Rainfall Intensity:
All exterior gutters and downspouts shall be designed in accordance with the provisions
of the code having jurisdictions.
10. Deflections shall be limited as follows:
The Live load Deflection of the primary and the secondary members shall be per latest
applicable ASCE7 standard.
Roof Members Not supporting Ceiling l/240.
Roof Members supporting plaster ceiling l/360.
Exterior Walls and Interior partitions l/240
11. Code Analysis:
Occupancy Category is designated as II
Use Group “S-1”.
Type of Construction “IIB
Occupancy load (Reduced) to 15 (total) per waiver approved by Loudoun County
Building Development Dated, November 16, 2012. A copy of approval is attached.
12. Thermal Effects:
Standing Seam roof panels shall be free to move in response to the expansion and
contraction forces resulting from a temperature variation.
The building is cold and not insulated, except for the office areas as shown on the
drawings.
Assembly to permit movement of components without buckling, failure of joint
seals, and undue stress on fasteners; insulation shall be provide to underside of
the roof to prevent excessive expansion and contraction.
13. Site Conditions:
The following site features and adjacent structures must be considered in the design.
The building will be adjacent to a hill, approximate drop in elevation 5’ to 6’. There are
few trees in the back of the building. The closest building to the new structure is about
50’ away.
Storage building:
The Storage building is separated into three areas; a 54’x28’ a 70’x53 and 55’x17’ areas. The total
area of the building is calculated to be 6157 sq. ft.
The building will house a very small amount of Hazardous materials; however, the amount is
well below the limits set for “H” use group and specified in IBC table 307.1 (1). A full listing of
these materials may be provided to the contractor upon request. The owner is responsible to
provide an adequate and NFPA approved storage area to store these materials.
Page 6/13
Edit Online
Free Download

Detailed Construction Scope of Work Template PDF

Favor this template? Just fancy it by voting!
  •  
  •  
  •  
  •  
  •  
(1 Votes)
5.0
Related Forms
  •  
  •  
  •  
  •  
  •  
2 Page(s) | 3591 Views | 117 Downloads
  •  
  •  
  •  
  •  
  •  
1 Page(s) | 2356 Views | 159 Downloads
  •  
  •  
  •  
  •  
  •  
4 Page(s) | 4891 Views | 104 Downloads
  •  
  •  
  •  
  •  
  •  
1 Page(s) | 14153 Views | 2664 Downloads
  •  
  •  
  •  
  •  
  •  
2 Page(s) | 4157 Views | 296 Downloads